| conversion | conversion | n/a |  |  | Clean pit of water and oil. Sump pump | 2/2/2021 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | Emergency light and alarm bell do not work. | 12/15/2020 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | Emergency phone does not work on 110V or regular power. Re-inspection required | 11/16/2021 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | x |  | Fire service key switch is broken from backet at main landing. | 12/15/2020 | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)1 |  |  | Pit is retaining water, need to provide means for water to be removed by the sump pump |  | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 |  |  | Provide current year tested fire extinguisher in the elevator machine room. |  | 
                
                    | A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x |  | Remove water from pit. | 1/28/2020 |