                        A17.1-1996 : Elevators
                     | 
                    
                        5.1 - Pit access, lighting, stop switch, and condition
                     | 
                    
                        106.1e Illumination of Pits
                     | 
                    
                     | 
                    
                     | 
                    
                        Repair and replace packing to reduce leaking and remove oil from pit.
                     | 
                    
                        7/15/2020
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency phone does not work, Re-inspection required
                     | 
                    
                        11/16/2021
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.32 - Control Valve 
                     | 
                    
                        3.19.4.3 Check Valve
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Failed leak down test due to check valve leakage. Re-inspection required
                     | 
                    
                        12/14/2023
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.7 - Fire Extinguisher
                     | 
                    
                        8.6.1.6.5
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide current year tested fire extinguisher in the elevator machine room.
                     | 
                    
                        
                     |