Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The unintended motion testing shall be performed before the inspection is completed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) There are a number of Braille floor indicating tags that are missing on multiple floors and shall be reinstalled for proper floor identification. 9/8/2020