A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
When testing the emergency power, the emergency power jewel at the main lobby failed to illuminate, needs repaired. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
Yes
|
No
|
When testing phase I fire service, the visual indicator light failed to illuminate, needs repaired. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
Elevator car door restrictor does not work, needs repaired. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
Yes
|
No
|
Elevator hoistway door safety retainers are missing on the 2nd and 7th floor hoistway doors, need repaired.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Elevator cab steadier bushing is missing from top of elevator car, needs repaired
|
|
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
No
|
No
|
There are a number of Braille floor indicating tags that are missing on multiple floors and shall be reinstalled for proper floor identification.
|
9/8/2020
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
6/3/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The unintended motion testing shall be performed before the inspection is completed.
|
6/3/2025
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
6/11/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed.
|
6/11/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required
|
6/22/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
|
6/22/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
Elevator car door restrictor does not work, needs repaired. Re-inspection required
|
7/29/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
No
|
No
|
Elevator hoistway door safety retainers are missing on the 2nd and 7th floor hoistway doors, need repaired.
|
7/29/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Elevator cab steadier bushing is missing from top of elevator car, needs repaired
|
7/29/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required
|
7/29/2026
|