| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform the following tests to complete CAt 5 full load test: Test drive machine brake with 125% of rated load, perform unintended movement test with 125% of rated load, test car safeties with rated load at rated speed, test car buffer at rated speed with rated load, test counterweight buffer at rated speed. Re-inspection required | 12/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work, possible electrical problem, needs repaired | 12/9/2025 |