Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) The machine room climate control shall be operational. 8/31/2020
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The materials and tools not necessary for the operation or maintenance of the elevator shall be removed from the machine room. 8/31/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Evacuation procedures shall be included in the MCP.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that is due for category 5 testing on or before the next annual inspection.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency battery lowering shall be operational. 8/31/2020