Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working. Re-inspection required 3/19/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV has no tag or seal. Re-inspection required 3/19/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x OSV needs to be tested in 90 days or less. Re-inspection required 3/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Unable to communicate with emergency personnel over phone, phone line is dead. Re-inspection required 6/13/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x OSV needs to be tested in 90 days or less. Re-inspection required 6/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV needs to be tested in 90 days or less. 6/13/2024