Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/12/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling panels in car are open egg crate type. Providing no protection for passengers in event of light bulb breakage. Replace with solid type panels or install plastic tubes and end caps on bulbs. 9/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x battery lowering device shall work. Repair/ replace same 9/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Need to perform required OSV testing within 90 days 9/20/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light not working 9/25/2020