Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x Per manufacturer's specifications the governor sheave shall be replaced within 6 months. 12/4/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x Per manufacturer's specifications, belt monitor indicates that the hoist belts need to be scheduled for replacement. 12/4/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x Phase 1 & 2 fire service shall be tested. 12/4/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x When tested it was determined the governor sheave did not meet specifications per the manufacturer. Replace the governor sheave per the manufacturers' specifications in the next 90 days. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a copy of the current state operating certificate. 3/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 3/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Fire Service operation shall be tested as required.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Water and oil shall not be allowed to accumulate on the pit floor.