A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
1001.2(a)(12)
|
|
|
Replace the missing hand rail in the car enclosure.
|
3/16/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In cab emergency telephone shall work.
|
12/4/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/19/2021
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
1001.2(b)(28)
|
x
|
|
Per manufacturer's specifications, the governor sheave shall be replaced within 6 months.
|
12/4/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Phase 1 & 2 fire service shall be tested.
|
12/4/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
The hoisway overhead lighting shall be operational.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
3/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
12/29/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
Fire service shall be tested to complete the annual inspection.
|
12/29/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
Fire Service operation shall be tested as required.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Water and oil shall not be allowed to accumulate on the pit floor.
|
|