Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (F) - Electrical Switches (F)1 x In car pull stop switch needs to be tied into the alarm bell. 6/16/2020
MO Minimum : Elevators (F) - Electrical Switches (F)1 x In car pull top switch needs to be accompanied by an alarm when activated. 9/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm and bell do not work. 9/23/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Suspension ropes need to be shortened. Car does not make up final limit on car top inspection. RED TAGGED. 9/23/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Anti spin out cable is broken. 2/2/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes need to be shortened. 6/16/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)2 Anti spin-out cable is broken. Needs to be replaced. 2/2/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x Door does not stay open during Phase II. 6/16/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Wrong key switch is in car for fire service. 6/16/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Door does not stay open during Phase I operation. RED TAGGED. 9/23/2020
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys x All fire recall switches in a building shall be keyed alike 11/5/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Standard receptical in the elevator cab shall be removed or replaced with a GFIC receptacle 11/5/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.5 x Repair and retest the Shunt trip circuit 11/5/2024
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 2.26.1 Shunt trip currently not functioning when car is on Fire recall bypass
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room illumination shall be 19fc minimum 11/5/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Supply permanent power to rescue phone. Extension cords do not meet the NFPA 70 codes 11/5/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys All elevators in a single building shall have Firerecall switches keyed alike
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys x All Fire recall key switches shall be keyed alike within 30 days. (12/20/24)
conversion conversion conversion - reinspect x Door Edge is not overridden on Phase 1 and 11 5/8/2019