MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
Anti spin out cable is broken.
|
2/2/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)2
|
|
|
Anti spin-out cable is broken. Needs to be replaced.
|
2/2/2021
|
A17.1-2016 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
2.26.1
|
|
|
Shunt trip currently not functioning when car is on Fire recall bypass
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys
|
|
|
All elevators in a single building shall have Firerecall switches keyed alike
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys
|
x
|
|
All Fire recall key switches shall be keyed alike within 30 days. (12/20/24)
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Door Edge is not overridden on Phase 1 and 11
|
5/8/2019
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Suspension ropes need to be shortened.
|
6/16/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Door does not stay open during Phase II.
|
6/16/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Wrong key switch is in car for fire service.
|
6/16/2020
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
In car pull stop switch needs to be tied into the alarm bell.
|
6/16/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Suspension ropes need to be shortened. Car does not make up final limit on car top inspection. RED TAGGED.
|
9/23/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Door does not stay open during Phase I operation. RED TAGGED.
|
9/23/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm and bell do not work.
|
9/23/2020
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
In car pull top switch needs to be accompanied by an alarm when activated.
|
9/23/2020
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room illumination shall be 19fc minimum
|
11/5/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
x
|
|
All fire recall switches in a building shall be keyed alike
|
11/5/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Supply permanent power to rescue phone. Extension cords do not meet the NFPA 70 codes
|
11/5/2024
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
x
|
|
Standard receptical in the elevator cab shall be removed or replaced with a GFIC receptacle
|
11/5/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.5
|
x
|
|
Repair and retest the Shunt trip circuit
|
11/5/2024
|