A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
9/18/2024
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
3.19.4.7.5(a)
|
x
|
|
Provide Cat 5 testing of OSV in the pit.
|
11/18/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
10/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide existing battery backup lowering unit to work properly.
|
11/18/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
x
|
|
This elevator has an overspeed valve device installed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required.
|
9/18/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
x
|
|
The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
|
9/18/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The category 5 testing has not been completed on the elevator at this time. The overspeed valve test shall be performed, standby power, and emergency lowering before the inspection is completed.
|
9/18/2024
|