MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
Yes
|
No
|
Could not test fire service phase 1 or 2, elevator shutdown during inspection
|
8/7/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Display Current State Operating Certificate in the Elevator Machine Room
|
5/18/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.3 Provide Auxiliary Lighting
|
Yes
|
No
|
Emergency lights did not come on, alarm bell worked
|
8/7/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
No
|
No
|
Label the elevator disconnect and the elevator light disconnect in the machine room with the panel name and breaker number that they are fed from
|
8/7/2026
|
|
A17.1-1996 : Elevators
|
2.40 - Maintenance Records
|
210.1d Inspection Operation.
|
No
|
No
|
No maintenance records on site or available
|
5/18/2026
|