ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
8.11.2.1.5(c)
|
|
|
8.6.2.1 The elevator pit and buffer channels are severely corroded and shall be cleaned, repaired, and painted with a rust inhibitor coating.
|
4/16/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
8.11.2.1.5(c)
|
|
|
8.6.3.1 The elevator pit and buffer channels are severely corroded and shall be cleaned, repaired, and painted with a rust inhibitor coating.
|
4/16/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Everything not related to the elevator shall be removed from the machine room.
|
10/10/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The ADA telephone inside the elevator is not working properly. Check and repair the phone line for proper operation and passenger safety. This will require a reinpection to verify compliance. (Correct Code: 8.10.2.2.1(f))
|
11/6/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
8.6.4.5
|
x
|
x
|
The elevator car safety assembly on the counterweight side failed to reset properly after performing the 5 year annual test. The safeties shall be repaired or replaced and reinspection performed.
|
2/22/2024
|