Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Wiring not related to the function of the elevator shall not be run through elevator hoistway.
conversion conversion conversion - reinspect x The existing cab emergency telephone does not work and shall be repaired and tested. 11/21/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a copy of the current state operating certificate.
MO Minimum : Elevators (A) - Hoistways (A)13 All the holes in the hoistway shall be sealed.
MO Minimum : Elevators (I) - Pits (I)1 Clean the upper pit of dirt and debris.
MO Minimum : Elevators (A) - Hoistways (A)17 Remove abandoned piping from the hoistway.
MO Minimum : Elevators (A) - Hoistways (A)16 Wiring at the top of the hoistway shall be enclosed in conduit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the elevator machine room is expired and shall be serviced or replaced.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The plastic waste pipe located above the controller shall be guarded or guttered.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational on 110v and battery. 2/25/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators (A) - Hoistways (A)13 Patch all holes in the hoistway.
MO Minimum : Elevators (I) - Pits (I)1 The upper pit shall be clean.
MO Minimum : Elevators (A) - Hoistways (A)17 Remove the abandoned piping from the hoistway.
MO Minimum : Elevators (A) - Hoistways (A)16 Wiring at the top of the hoistway shall be enclosed.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The plastic waste pipe located above the pump unit shall be guarded or guttered.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency phone shall be operational. 9/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency lighting shall be operational. 9/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency lighting shall be operational. 11/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall work on auxiliary power. 11/2/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be displayed in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The car top shall be kept clean. Clean the car top.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Elevator quit running in middle of the inspection. Still need to do relief pressure, standing test, 110v and fire service. 11/7/2024