Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 4.2 - Hoistway doors 210.2 No No Replace broken door closer. 1/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written maintenance control program shall be provide for each elevator on site. 1/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage No No Scavenger pumps that do not record amount of oil to be returned to the tank cannot be installed in the elevator pit. 1/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No There is a scavenger pump in the pit that must be replaced with a 5 gallon bucket in order to record oil leakage 6/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A copy of the MCP shall be kept in the machine room for each elevator 1/27/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 1/27/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Access to machine room shall be kept clear & unobstructed 1/27/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 1/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Unit has oil scavenger pump in pit. Remove pump and replace with proper container so oil leakage from cylinder can be measured 1/27/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone in elevator cab does not work. 5/22/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No A17.1-1996 : Elevators 1.6 - Car emergency signal 1201.2(a)(6) Phone in elevator cab does not work. 11/25/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone in elevator cab does not work. 12/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light does not work on 110v emergency power 12/5/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in the cab does not work. Reinspection required in 14 days 1/16/2025