A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Replace compensation wire ropes from car to counterweight. Ropes are badly rouged and have valley breaks.
|
6/13/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency phone.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.13 - Emergency exit
|
8.11.2.1.1(m)
|
|
|
Access switch is not connected.
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove the water from the pit.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(b)
|
|
|
MCP shall list associated requirement of section 8.6
|
3/24/2023
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
MRL shall list requirements of 8.6 for each task, test, and specify scheduled intervals.
|
3/24/2023
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
3/24/2023
|
|
conversion
|
conversion
|
n/a
|
|
|
Rear car gate vision panel cracked. Vision panel needs to be replaced.
|
7/27/2020
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(b)
|
|
|
The written MCP needs to specify the maintenance tasks, and tests, and shall list the associated requirement of section 8.6.
|
6/9/2023
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Written maintenance records shall list the requirement of section 8.6 that pertains to the task, and tests, with specified scheduled intervals.
|
6/9/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State certificate not displayed.
|