Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. 6/6/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the emergency phone shall be answered 24/7, this phone is calling 911, and they are unable to communicate with passengers in elevator. 4/10/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV not sealed. Perform OSV test on or before next annual inspection. 11/2/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Remove any non elevator related equipment from the elevator machine room 4/22/2024
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 1001.2(c)(3) Car top inspection station shall work. 6/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 11/2/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 4/22/2024