Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light & receptacle are not working, needs repaired 3/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit appears to have emergency generator power, which needs to be tested. Re-inspection required 11/21/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Written maintenance control program shall be kept on site for each elevator. 12/14/2022
A17.1-2016 : Elevators 3.29 - Counterweight safeties 8.11.2.1.3(n) x x Counterweight seismic displacement does not work. Repair within 30 days. Did not red tag elevator. 3/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room 3/17/2023