Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light not working on battery back up. 12/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) Repair door open button in fire panel inside of car. 12/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Door open button in fire service panel does not work on Phase II fire service. 12/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Maintenance records shall be kept on site 12/14/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room 3/17/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light & receptacle are not working, needs repaired 3/17/2023
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing wireway cover in overhead above top door hanger 3/17/2023
MO Minimum : Elevators (A) - Hoistways (A)16 Conduit going to governor tension switch is rusted out, exposing conductors. Replace conduit with more applicable material for conditions. 3/17/2023
MO Minimum : Elevators (A) - Hoistways (A)1 Replace missing wireway cover in overhead above top door hanger 11/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit appears to have emergency generator power, which needs to be tested. Re-inspection required 5/8/2025