Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car is not working. Re-inspection required 4/29/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Light bulbs in car requires protection, such as plastic tubes and end caps or solid ceiling panels to protect passengers in event of bulb breakage. 3/17/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Replace ceiling panels or guard light bulbs. 3/17/2026
MO Minimum : Elevators (D) - Brakes (D)2 Yes Yes The elevator failed the 125% brake test. Unit Red Tagged. 2/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light in car is not working. Re-inspection required 4/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 9/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, have serviced or replaced 3/17/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 3/17/2026
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. 3/17/2026
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Door open button still not working on initial recall in Phase 1. 7/25/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Door detector (light ray) shall not open the door in Phase 1. 7/25/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current MO.State operating certificate in machine room,
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current operating certificate shall be displayed in the machine room 3/17/2026