Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A17.1 - 2004 8.6.1.2 GENERAL MAINTENANCE REQUIREMENTS 8.6.1.2.1(1)(b) INSTRUCTIONS FOR LOCATING REMOTELY KEPT MCP RECORDS SHALL BE PROVIDED IN OR ON THE CONTROLLER. 7/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A17.1 - 2004 8.6.1.6 GENERAL MAINTENANCE METHODS & PROCEDURES PRINTED CAT 1 HYDRAULIC TEST PROCEDURES & OVERSPEED VALVE TESTING PROCEDURES ARE REQUIRED IN CONTROLLER. 7/9/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing A17.1 - 8.6.5.16.5 OVERSPEED VALVE NOT SEALED, PERFORM REQUIRED 5 YR OSV TESTING WITHIN 90 DAYS, PER MISSOURI DEPARTMENT OF FIRE SAFETY/ ELEVATOR SAFETY DIVISION 5/18/2022