Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Pit must be kept free of excessive water and debris. 7/13/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The car-top light shall be operational. 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No 8.11.2.1.1(b) - The in car stop switch shall be repaired or replaced. (The stop switch failed intermittently (open in the run position)). 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No 8.11.2.1.3(r) - The covers shall be properly installed on the car-top landing unit. 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No 8.11.2.1.3(w) - The broken pickup roller assembly at 2E shall be replaced. 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 3/29/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire service is not working. Violation must be corrected within 14 days or elevator will be red tagged and locked out of service. 11/4/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/29/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/29/2024
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No The fire service visual and audible alerts in the car shall be functional. 7/8/2024
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No The fire service visual alert at the egress floor shall be functional. 7/8/2024
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes All car call security lockouts shall be rendered inoperative on phase 2 fire service. This is the only working car in the building so the elevator was NOT red tagged. 3/29/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No The governor rope and the suspension ropes shall be tagged as specified by CSR 40-5.065(L)1 3/29/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 5/16/2019
MO Minimum : Elevators (I) - Pits (I)1 No No The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 5/16/2019
MO Minimum : Elevators (I) - Pits (I)1 No No Water and oil shall not be allowed to accumulate on pit floors. (The pit has at least 1 foot of water in it). 3/29/2024
MO Minimum : Elevators (I) - Pits (I)1 No No The pit light shall be operational. 3/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Safe access to the machine room shall be provided. (The path to the machine room involves ascending a ladder in an unlighted space, and moving through the unlighted machine room of the service elevator that is not in service to get to the roof). 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light and bell must work when cab does not have 110 VAC lighting. 7/13/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The complete annual and category 5 test that was originally scheduled for 9/12/24 is still due and was stopped due to fire service not working. 11/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The in car keyed stop switch shall be repaired or replaced. (The switch failed in a way that which made phase 2 fire service inoperable). 7/8/2024