ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not work, no power on the phone line
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
fire service test log is to be filled out monthly, currently only filled out quarterly
|
3/9/2020
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.3.1.1(e)
|
|
|
replace cab ceiling light bulbs that are burnt out
|
2/16/2021
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.3.1.2(b)
|
|
|
machine room door will not lock, the door jamb hole for the lock does not line up with the locking mechanism on the door
|
2/16/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
the monthly fire service test log is not being filled out
|
2/16/2021
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the state operating certificate is to be posted in the elevator machine room
|
2/16/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
did not have current maintenance log in the machine room
|
3/1/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
monthly fire service log is not being filled out
|
3/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
only das one working light bulb in the elevator cab, required to have two working light bulbs
|
5/17/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not work. No dial Town on the phone line provide working phone line.
|
2/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine room fire extinguisher was last inspected in 2022, have the fire extinguisher inspected annually
|