Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post a copy of the state operating certificate in the elevator machine room 2/16/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 fire service test log is to be filled out monthly, currently only filed in quarterly 3/9/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log is not being filled out 2/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light is burnt out, replace pit light bulb 3/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine room fire extinguisher was last inspected in 2022, have the fire extinguisher inspected annually 3/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(k) Mark the location of the feeder circuits for the main line and 110 discount in the machine room with the panel and breaker number they are fed from
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone line for the emergency phone is dead, provide working phone line to the elevator controller 5/3/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line is dead, provide working phone line 3/29/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps Replace burnt out cab ceiling light, required to have two working lightbulbs 3/20/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log has not been filled out 3/1/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light is burnt out, replace pit light bulb 4/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records does not have a 2021 or 2022 maintenance log in the machine room 3/1/2022