Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone line for the emergency phone is dead, provide working phone line to the elevator controller 5/3/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 fire service test log is to be filled out monthly, currently only filed in quarterly 3/9/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log is not being filled out 2/16/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post a copy of the state operating certificate in the elevator machine room 2/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records does not have a 2021 or 2022 maintenance log in the machine room 3/1/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log has not been filled out 3/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line is dead, provide working phone line 3/29/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps Replace burnt out cab ceiling light, required to have two working lightbulbs 3/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine room fire extinguisher was last inspected in 2022, have the fire extinguisher inspected annually 3/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light is burnt out, replace pit light bulb 3/20/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light is burnt out, replace pit light bulb 4/28/2025