Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate. 5/1/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintenance control plan on site 12/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) Water is leaking through the top of the hoistway enclosure and onto the top of the elevator. 2/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.5 - Traveling cables 8.11.3.1.5(f) Traveling cable needs to be replaced. Traveling cable is damaged due to moisture issue. 12/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 4/17/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x PROVIDE A WORKING IN CAR EMERGENCY PHONE
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Post In Case of Fire Do Not Use Elevator signage next to hall button fixture at bottom landing. 12/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside machine room 2/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 2.12.7 No hoistway access operation provided. 12/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x No firefighter phase 2 operation panel behind locked cover on car operating panel. 3/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door needs to be self locking and non-defeatable. 2/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 Identify the inside of hoistway doors with a numeral 12/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 Identify inside of the hoistway door with a numeral 4/17/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.2.1 Gas powered snowblower, container of gasoline, and bags of salt must be removed from elevator machine room. Non-elevator related material shall not be stored inside the machine room. Extreme fire hazard. 2/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not provide two way communication 2/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate. 12/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.3.5 x BATTERY ENERGENCY LOWERING NOT WORKING
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x 2.27.3.3.1(c) Door close button non functional must reinspect when issue is corrected. 3/29/2024