ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
x
|
|
2.27.3.3.1(c) Door close button non functional must reinspect when issue is corrected.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.3.5
|
x
|
|
BATTERY ENERGENCY LOWERING NOT WORKING
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate.
|
12/20/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate.
|
5/1/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not provide two way communication
|
2/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.2.1
|
|
|
Gas powered snowblower, container of gasoline, and bags of salt must be removed from elevator machine room. Non-elevator related material shall not be stored inside the machine room. Extreme fire hazard.
|
2/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
|
|
Identify inside of the hoistway door with a numeral
|
4/17/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
|
|
Identify the inside of hoistway doors with a numeral
|
12/28/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door needs to be self locking and non-defeatable.
|
2/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
x
|
|
No firefighter phase 2 operation panel behind locked cover on car operating panel.
|
3/24/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
2.12.7
|
|
|
No hoistway access operation provided.
|
12/28/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No maintenance control plan on site
|
12/28/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside machine room
|
2/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
|
|
Post In Case of Fire Do Not Use Elevator signage next to hall button fixture at bottom landing.
|
12/28/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
PROVIDE A WORKING IN CAR EMERGENCY PHONE
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
4/17/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.5 - Traveling cables
|
8.11.3.1.5(f)
|
|
|
Traveling cable needs to be replaced. Traveling cable is damaged due to moisture issue.
|
12/28/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
|
|
Water is leaking through the top of the hoistway enclosure and onto the top of the elevator.
|
2/15/2022
|