A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
Yes
|
No
|
OSV is due to be tested, perform required testing this year. Re-inspection required
|
8/4/2022
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.27
|
Yes
|
No
|
Need to perform the required Cat 1 emergency generator testing to complete the annual testing. Re-inspection required
|
3/10/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Elevator main lobby shall have a generator power bezel labeled "ELEVATOR EMERGENCY POWER". Re-inspection required
|
|