Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 8.11.2.1.1(p) There car capacity plate inside the elevator stating the rated load of the car is unreadable and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The rear car door direction arrow has been damaged and shall be replaced to operate as required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fireman's emergency service instructions are unreadable inside the car and shall be replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The elevator machine room door shall be repaired to be self-closing and self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate needs to be posted in the machine room in a non-combustible frame.
conversion conversion n/a Repair cab emergency lights 7/23/2018
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required 12/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Need to replace direction arrow in cab, front & back
conversion conversion n/a Clean oil from elevator pit. 7/23/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting x Auxiliary lighting inoperable, repair or replace. 2/21/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working when the power is off. Re-inspection required 10/23/2023