Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working when the power is off. Re-inspection required 10/23/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting x Auxiliary lighting inoperable, repair or replace.
conversion conversion n/a Clean oil from elevator pit. 7/23/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Need to replace direction arrow in cab, front & back
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required 12/20/2022
conversion conversion n/a Repair cab emergency lights 7/23/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate needs to be posted in the machine room in a non-combustible frame.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The elevator machine room door shall be repaired to be self-closing and self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fireman's emergency service instructions are unreadable inside the car and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The rear car door direction arrow has been damaged and shall be replaced to operate as required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 8.11.2.1.1(p) There car capacity plate inside the elevator stating the rated load of the car is unreadable and shall be replaced.