Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Pit needs to be cleaned. 2/14/2020
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 1005.2b Jack packing needs to be repaired. 3/3/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light not working. 3/3/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean oil and debris from pit. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Sump hole is filled with oil, remove. Determine if the sump pump still works, if not replace.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals x Left cylinder is leaking a lot of oil causing the pit to be full of oil. Packing or cylinder shall be repaired before returning to service. Unit was not Safe to inspect. RED TAG 4/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Annual inspection was not performed due to red tag on cylinder. Complete annual inspection 4/12/2023