Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Rear car door safety edge does not repen the doors 9/30/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-closing.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-closing
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-closing
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door shall be self-closing
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove non-elevator related material from machine room
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to hall fire keyswitch
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate inside machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No maintenance control plan in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No MCP
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Post emergency evacuation of passengers form inside machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Written log of hydraulic oil usage needs to be kept in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No maintenance records on site
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No maintenance record log in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly.