Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Overspeed valve shall be tested with the rated load on or before the next annual test.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Machine room has a sprinkler, but no heat detector and no apparent shunt trip. When a sprinkler is present in the machine room it shall be equipped with means to remove main power before discharging water.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/8/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h The fire extinguisher is expired.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The state operating certificate is expired.