Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Door motor wiring on top of car needs to be in metal conduit. Install missing covers on pullboxes on top of elevator.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide ABC fire extinguisher in elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Eliminate gap between horizontal sliding 2 speed hoistway doors at bottom landing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) Install metal test tag documenting periodic testing
MO Minimum : Elevators (I) - Pits (I)3 Install counterweight guard.
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)5 Install warning chains on bottom side of elevator platform.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Gradual wedge clamp safety stopping distance with no load exceeds 74 inches.
conversion conversion n/a Door reopening device working intermittently. Need to repair or replace same. 7/24/2018