Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be made operational. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Low oil timer shall work. 2/22/2019
MO Minimum : Elevators (I) - Pits (I)1 No No Clean pit. 8/11/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be clean and kept clean of all debris and water
A17.1-2016 : Elevators 1.14 - Ventilation 2.14.2.3 No No A/C unit above door has condensation running down, puddling onto machine room floor. Repair as needed.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.3.1.1(q) Yes No Battery lowering not working needs an auxiliary contact in the disconnect 6/22/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work properly. 7/11/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Phone line loss lobby unit not working, repair as needed. 7/11/2024
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 3.26.1 No No Machine room heater shall be wired to meet NFPA 70 8/11/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 3.7.1 Yes No Increase Machine room Illumination to 19ft candles 8/11/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 No No No water conveying devices allowed in the machine room. This is a mod with exisiting pipes in the machine room. Must apply for a varience. Due to size of the machine room encapsulation is not an option. 8/11/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 Yes No Machine room door has fire rated damper removed negating the fire rating 6/22/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No A written maintenance control program shall be kept on site and kept up to date
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 Yes No Microprocessor controller requires HVAC for temperature and humidity control 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No Label Mainline and 110 volt disconnects with feeder locations 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No Cover open knock outs in GFIC box 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 Yes No Electric base board heater has exposed wiring 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No Mainline under fused controller spec's call for 100amp fusing pump and controller have peak draw of 72amps. fused at 70amps 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 No No Label the disconnect with location of power source 8/11/2022
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 2.1.1 Yes No Close holes above hall stations to maintain hoistway fire rating 6/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 3.2 Yes No Increase pit illumination to 10 foot candles 8/11/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 3.2 Yes No Pit light wiring required to be in conduit by NFPA 70 8/11/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No Pit illumination shall be 10 ft candles minimum 6/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 Yes No Pit lighting shall be hard wired 6/22/2022