Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.14 - Ventilation 2.14.2.3 A/C unit above door has condensation running down, puddling onto machine room floor. Repair as needed.
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be clean and kept clean of all debris and water
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A written maintenance control program shall be kept on site and kept up to date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Low oil timer shall work. 2/22/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.3.1.1(q) x Battery lowering not working needs an auxiliary contact in the disconnect 6/22/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Machine room door has fire rated damper removed negating the fire rating 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Electric base board heater has exposed wiring 6/22/2022
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Microprocessor controller requires HVAC for temperature and humidity control 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Label Mainline and 110 volt disconnects with feeder locations 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Cover open knock outs in GFIC box 6/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit illumination shall be 10 ft candles minimum 6/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x Pit lighting shall be hard wired 6/22/2022
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 2.1.1 x Close holes above hall stations to maintain hoistway fire rating 6/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Mainline under fused controller spec's call for 100amp fusing pump and controller have peak draw of 72amps. fused at 70amps 6/22/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 3.7.1 x Increase Machine room Illumination to 19ft candles 8/11/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 3.2 x Increase pit illumination to 10 foot candles 8/11/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 3.2 x Pit light wiring required to be in conduit by NFPA 70 8/11/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Label the disconnect with location of power source 8/11/2022
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 3.26.1 Machine room heater shall be wired to meet NFPA 70 8/11/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 No water conveying devices allowed in the machine room. This is a mod with exisiting pipes in the machine room. Must apply for a varience. Due to size of the machine room encapsulation is not an option. 8/11/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. 8/11/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work properly. 7/11/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Phone line loss lobby unit not working, repair as needed. 7/11/2024