A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
A written maintenance control program shall be kept on site and kept up to date
|
|
A17.1-2016 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
|
|
A/C unit above door has condensation running down, puddling onto machine room floor. Repair as needed.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.3.1.1(q)
|
x
|
|
Battery lowering not working needs an auxiliary contact in the disconnect
|
6/22/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit.
|
8/11/2022
|
A17.1-2016 : Elevators
|
4.8 - Hoistway enclosure
|
2.1.1
|
x
|
|
Close holes above hall stations to maintain hoistway fire rating
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Cover open knock outs in GFIC box
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Electric base board heater has exposed wiring
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
3.7.1
|
x
|
|
Increase Machine room Illumination to 19ft candles
|
8/11/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
3.2
|
x
|
|
Increase pit illumination to 10 foot candles
|
8/11/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Label Mainline and 110 volt disconnects with feeder locations
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
|
|
Label the disconnect with location of power source
|
8/11/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Low oil timer shall work.
|
2/22/2019
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Machine room door has fire rated damper removed negating the fire rating
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
3.26.1
|
|
|
Machine room heater shall be wired to meet NFPA 70
|
8/11/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Mainline under fused controller spec's call for 100amp fusing pump and controller have peak draw of 72amps. fused at 70amps
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
Microprocessor controller requires HVAC for temperature and humidity control
|
6/22/2022
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
|
|
No water conveying devices allowed in the machine room. This is a mod with exisiting pipes in the machine room. Must apply for a varience. Due to size of the machine room encapsulation is not an option.
|
8/11/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Phone line loss lobby unit not working, repair as needed.
|
7/11/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit illumination shall be 10 ft candles minimum
|
6/22/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
3.2
|
x
|
|
Pit light wiring required to be in conduit by NFPA 70
|
8/11/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
Pit lighting shall be hard wired
|
6/22/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be clean and kept clean of all debris and water
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work properly.
|
7/11/2024
|