Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 No No Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency bell is not working on battery back up.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light is not working on battery back up.
conversion conversion n/a No No Post current state certificate in machine room 4/25/2019
conversion conversion n/a No No Remove cover on lobby smoke detectors at the 3rd, 5th, 7th, & 8th floors 4/25/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need a maintenance control program on site posted on controller 7/15/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 7/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Repair phone in car 7/15/2021
MO Minimum : Elevators (J) - Counterweights (J)1 No No Top right counterweight needs replacing 5/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete need to crush car buffer and perform slide test 5/28/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service test and document on log in machine room 6/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Investigate and repair severe motor coupling noise. 4/13/2026