Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil recovery systems that return hydraulic fluid back to the main reservoir by automatic means or by gravity are not allowed. Oil leakage collected from the cylinder packing gland shall not exceed 5 gallons before removal, and a written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The container for collecting oil shall not be permitted to overflow.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Discharge line on sump pump sprays water all over the pit. This shall be corrected.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested, ABC type fire extinguisher shall be provided in the elevator machine room. 3/13/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 3/13/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. 3/13/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 1/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 1/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Slack cable switch did not work on unit. Red tagged out of service. 11/20/2024