Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) A capacity plate shall be posted in the car. 1/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.2 - Stop switches 8.11.3.1.1(b) (Re-Inspection) x The in car stop switch is damaged and shall be repair or replaced as needed. The stop switch shall be tested once repaired or replaced. 4/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/17/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone has incorrect car number, repair as needed. 4/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 7/21/2023
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 1001.2(c)(15) The car top shall be correctly numbered. 1/23/2023
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 211.9 Provide numbering of the elevator inside the car. 1/23/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Replace means to identify COP phase 2 fire service panel. *Note* - All signs and labels on car COP have been removed, determine if any other other labels or signs are missing and replace as needed, per manufacturer specifications. 1/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state operating certificate shall be obtained and displayed in the elevator machine room. 7/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/10/2024