Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Suspension ropes need to be shortened. Re-inspection required 9/13/2023
MO Minimum : Elevators (I) - Pits (I)4 Counterweight compresses buffer more than 25% while reaching final terminal switch
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The phone needs to call someone that will answer 24/7. This phone is programmed to call the front desk, no one answered. Re-inspection required 4/3/2024