Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)4 No No Counterweight compresses buffer more than 25% while reaching final terminal switch 11/13/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes No Suspension ropes need to be shortened. Re-inspection required 9/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The phone needs to call someone that will answer 24/7. This phone is programmed to call the front desk, no one answered. Re-inspection required 4/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Yes No Runby is 1". Hoist ropes shall be shortened for proper runby.