Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (I) - Pits | (I)4 | Counterweight compresses buffer more than 25% while reaching final terminal switch | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The phone needs to call someone that will answer 24/7. This phone is programmed to call the front desk, no one answered. Re-inspection required | 4/3/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Suspension ropes need to be shortened. Re-inspection required | 9/13/2023 |