MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work.
|
7/11/2024
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
The in car emergency stop switch (toggle) is broken and shall be replaced or repaired.
|
4/4/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
8.6.5.8 - Possible single bottom jack. Based off of serial number unit is likely a double bottom type. Submit documentation to the state and leave documentation on site that confirms jack type.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Possible single bottom jack. Provide documentation that hydraulic jack is of double bottom type or perform necessary correction.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall be guarded to prevent breakage or accidental contact.
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.14.2 Hydraulic Cylinders and Pressure Piping
|
x
|
x
|
Excessive oil leaking from the jack. Jack is blown. Elevator Red Tagged.
|
9/2/2021
|
conversion
|
conversion
|
n/a
|
|
|
Possible single bottom jack.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be obtained and displayed in the elevator machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a copy of the current state operating certificate.
|
|