Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.14.2 Hydraulic Cylinders and Pressure Piping x x Excessive oil leaking from the jack. Jack is blown. Elevator Red Tagged. 9/2/2021
conversion conversion n/a Possible single bottom jack.
MO Minimum : Elevators (F) - Electrical Switches (F)1 x The in car emergency stop switch (toggle) is broken and shall be replaced or repaired. 4/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance 8.6.5.8 - Possible single bottom jack. Based off of serial number unit is likely a double bottom type. Submit documentation to the state and leave documentation on site that confirms jack type.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be guarded to prevent breakage or accidental contact.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a copy of the current state operating certificate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Possible single bottom jack. Provide documentation that hydraulic jack is of double bottom type or perform necessary correction.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. 7/11/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.