ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working
|
8/29/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Machine room lights all shall work and have 10 fc of light.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
A17.1S - 2005 - 2.7.9.1 - Machine/control spaces or rooms lighting need to be at least 19fc at the floor level. (Previously incorrectly cited as 10fc). Note: This unit is an MRL
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
A17.1S - 2005 - This unit is an MRL and there is no GFI receptacle or lights in overhead which is a machine space.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Inspection incomplete - Elevator was left shut down due to software issues and bad card. Fire service still needs to be tested as well as the entire category 5 test.
|
11/8/2024
|