Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone not working 8/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Machine room lights all shall work and have 10 fc of light.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting A17.1S - 2005 - 2.7.9.1 - Machine/control spaces or rooms lighting need to be at least 19fc at the floor level. (Previously incorrectly cited as 10fc). Note: This unit is an MRL
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 A17.1S - 2005 - This unit is an MRL and there is no GFI receptacle or lights in overhead which is a machine space.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Inspection incomplete - Elevator was left shut down due to software issues and bad card. Fire service still needs to be tested as well as the entire category 5 test. 11/8/2024