Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No Overspeed valve is due to be tested in 2021. Perform required testing, seal & tag on or before next annual inspection 11/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation No No Repair or replace smoke detector in machine room 10/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, have serviced or replaced 10/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No A written maintenance control program shall be kept on site 1/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be made operable. Re-inspection required 9/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Cab ceiling panels are open egg crate type, providing no protection for passengers. Replace panels with solid type or install plastic tubes and endcaps over bulbs 1/4/2024