Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Junction box too small for the number of wires and unit covered Extend box and cover NEC 8/24/2018
conversion conversion n/a No No Secure conduit to the machine room wall NEC 8/24/2018
conversion conversion n/a No No Mount machine room light fixture. Fixture hanging by wires NEC 8/24/2018
conversion conversion n/a No No Repair inoperative emergency light 8/24/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door must be self-locking 5/7/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No MCP needed 5/7/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm bell not working. Battery
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light not working. Battery