Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be displayed in machine room. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on-site. 9/27/2022
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV sealed, no tag. Due for testing. 11/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Provide means to collect oil in the pit from each piston. Remove lines going back to tank. 11/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A current test & tagged ABC type fire extinguisher shall be provided in the machine room. 11/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 11/7/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x The elevator is equipped with an overspeed valve. Category 5 testing was due in 2022. A category 5 test of the overspeed valve shall be completed within 90 days. 11/7/2023