Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)2 No No Repair car buffer, set-bolt is stripped. 1/6/2026
MO Minimum : Elevators (I) - Pits (I)2 No No Repair car buffer, set-bolt is stripped. 1/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be displayed in the elevator machine room. 1/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No The fire extinguisher in the machine room is expired and shall be serviced or replaced with another code compliant fire extinguisher. 12/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 1/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be displayed in the elevator machine room. 1/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 1/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service testing shall be documented monthly. 1/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals Yes No The hydraulic cylinder packing is leaking excessively and corrective action shall be taken. 12/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone will not dial out. Take corrective action and re-test. 1/31/2025